EXPERIMENTAL STUDY ON BEHAVIOR OF UNPROTECTED FOAMED CONCRETE FILLED STEEL HOLLOW COLUMN UNDER FIRE

  • Bishir Kado Civil Engineering Department, Faculty of Engineering, Bayero University, Kano-Nigeria.
  • Shahrin Mohammad School of Civil Engineering, Universiti Teknologi Malaysia, 81310 Johor Bahru, Johor, Malaysia.
  • Yeong Huei Lee Department of Civil and Construction Engineering, Faculty of Engineering and Science, Curtin University Malaysia, CDT 250, 98009 Miri, Sarawak, Malaysia.
  • Poi Ngian Shek Construction Research Centre (UTM-CRC), Universiti Teknologi Malaysia, 81310 Johor Bahru, Johor, Malaysia
  • Mariyana Aida Ab Kadir School of Civil Engineering, Universiti Teknologi Malaysia, 81310 Johor Bahru, Johor, Malaysia.
Keywords: Fire resistance, Foamed concrete filled column, hollow column, unprotected foamed concrete filled column, temperature

Abstract

Reduction in self-weight and achievement of full fire resistance requirements are some of the important considerations in the design of high-rise structures. Lightweight concrete filled steel tube (CFST) column provides an alternative method to serve these purposes. Recent studies on lightweight CFST columns at ambient temperature have revealed that foamed concrete can be a beneficial and innovative alternative material. Hence, this study investigates the potential of using foamed concrete in circular hollow steel columns for improving fire resistance. A series of nine fire test on circular unfilled hollow and foamed concrete filled hollow section column were carried out. ISO 834 standard fire exposure test were carried out to investigate the structural response of these columns under fire. The main parameters considered are load level and foamed concrete density; foamed concrete density used are 1500 kg/m3 and 1800 kg/m3 at 15%, 20%, and 25% load level. All the columns tested are without any external fire protection, with concentrically applied load under fixed-fixed boundary conditions. The columns dimension was 2400 mm long, 139.7 mm diameter and steel tube thickness of 6 mm. The fire test result showed that foamed concrete increases the fire resistance of steel hollow column up to an additional 16 minutes. The improvement is more at load level above 15%, and the gain in fire resistance is about 71% when 1500 kg/m3 density foamed concrete is used. Generally, foamed concrete filled steel hollow column demonstrate a good structural fire behavior, based on the applied load and foamed concrete density. Also, inward local buckling was averted by filling the steel hollow column with foamed concrete. General method for composite column design in Eurocode 4 adopted to calculate the axial buckling load of 1500 kg/m3 foamed concrete filled columns.  These type of columns can be used for structures like airports, schools, and stadiums; taking the advantage of exposed steel for aesthetic purpose and high fire resistance. It can also be used for high rise structures; taking advantage of high fire resistance and reduction in self-weight of a structure.

References

J. Wardenier, Hollow Sections in Structural Applications. CIDECT, 2001.

L. Twilt, R. Hass, W. Klingsch, M. Edwards, and D. Dutta, Design Guide For structural hollow section columns exposed to fire. Germany: CIDECT Verlag TUV Rheinland, 1994.

V. Kodur, "Guidelines for Fire Resistant Design of Concrete-Filled Steel HSS Columns - State-of-the-Art and Research Needs," steel Struct., vol. 7, pp. 173-182, 2007.

V. K. R. Kodur and D. H. Mackinnon, "Design of concrete-filled hollow structural steel columns for fire endurance," Eng. Journal-American Inst. steel Constr., vol. 37, no. 1, pp. 13-24, 2000.

V. K. R. Kodur and T. T. Lie, "Fire performance of concrete-filled hollow steel columns," J. Fire Prot. Eng., vol. 7, no. 3, pp. 89-97, 1995.

https://doi.org/10.1177/104239159500700302

M. L. Romero et al., "Fire behavior of axially loaded slender high strength concrete-filled tubular columns," J. Constr. Steel Res., vol. 83, no. 67, pp. 1953-1965, 2011.

https://doi.org/10.1016/j.jcsr.2011.06.012

A. Espinos, M. L. Romero, A. Hospitaler, C. Ibanez, A. Pascual, and V. Moliner, Tubular Structures XIV Proceedings of the 14th International symposium on Tubular structures,. London UK: CRC PressTaylor and Francis Group, 2012.

K. U. Ukanwa, U. Sharma, S. J. Hicks, A. Abu, J. B. P. Lim, and G. C. Clifton, "Behaviour of continuous concrete filled steel tubular columns loaded concentrically in fire," J. Constr. Steel Res., vol. 136, no. May, pp. 101-109, 2017.

https://doi.org/10.1016/j.jcsr.2017.05.011

H. Guo, X. Long, and Y. Yao, "Fire resistance of concrete filled steel tube columns subjected to non-uniform heating," J. Constr. Steel Res., vol. 128, pp. 542-554, 2017.

https://doi.org/10.1016/j.jcsr.2016.09.014

N. Tondini, V. L. Hoang, J.-F. Demonceau, and J.-M. Franssen, "Experimental and numerical investigation of high-strength steel circular columns subjected to fire," J. Constr. Steel Res., vol. 80, pp. 57-81, 2013.

https://doi.org/10.1016/j.jcsr.2012.09.001

K. Wang and B. Young, "Fire resistance of concrete-filled high strength steel tubular columns," Thin-Walled Struct., vol. 71, pp. 46-56, 2013.

https://doi.org/10.1016/j.tws.2013.05.005

M. M. A. Ghannam, "Behaviour of Concrete-Filled Stainless Steel Columns Under Fire," University of Western Sydney, Australia, 2015.

L. Han, X. Zhao, Y. Yang, and J. Feng, "Experimental Study and Calculation of Fire Resistance of Concrete-Filled Hollow Steel Columns," J. Struct. Eng., vol. 129, no. 3, pp. 346-356, 2003.

https://doi.org/10.1061/(ASCE)0733-9445(2003)129:3(346)

Y. M. Hunaiti, "Strength of composite sections with foamed and light weight aggregate concrete," J. Mater. Civ. Eng., vol. 9, no. 2, pp. 58-61, 1997.

https://doi.org/10.1061/(ASCE)0899-1561(1997)9:2(58)

S. Ghannam, "Buckling of Concrete-Filled Steel Tubular Slender Columns," Int. J. Res. Civ. Eng. Archit. Des., vol. 3, no. 1, pp. 41-47, 2015. Doi: 10.3846/jcem.2010.26

https://doi.org/10.3846/jcem.2010.26

S. Ghannam, A.-R. Orabi, and M. El-khatieb, "Experimental Study on Light Weight Concrete-Filled Steel Tubes," Jordan J. Civ. Eng., vol. 5, no. 4, pp. 521-529, 2011.

T. Chan, Y. Huai, and W. Wang, "Experimental investigation on lightweight concrete- filled cold-formed elliptical hollow section stub columns," J. Constr. Steel Res., vol. 115, pp. 434-444, 2015.

https://doi.org/10.1016/j.jcsr.2015.08.029

E. P. Kearsley and P. J. Wainwright, "The effect of porosity on the strength of foamed concrete," Cem. Concr. Res., vol. 32, no. 2, pp. 233-239, 2002.

https://doi.org/10.1016/S0008-8846(01)00665-2

E. P. Kearsley, a. S. Tarasov, H. F. Mostert, and a. S. Kolomatskiy, "Heat evolution due to cement hydration in foamed concrete," Mag. Concr. Res., vol. 62, no. 12, pp. 895-906, 2010.

https://doi.org/10.1680/macr.2010.62.12.895

E. P. Kearsley and P. J. Wainwright, "Porosity and permeability of foamed concrete," Cem. Concr. Res., vol. 31, no. 5, pp. 805-812, 2001.

https://doi.org/10.1016/S0008-8846(01)00490-2

S. K. Lim, C. S. Tan, X. Zhao, and T. C. Ling, "Strength and toughness of lightweight foamed concrete with different sand grading," KSCE J. Civ. Eng., vol. 19, no. 7, pp. 2191-2197, 2014.

https://doi.org/10.1007/s12205-014-0097-y

BS EN1993-1-1, "Eurocode 3: Design of steel structures- Part 1-1 General rules and rules for buildings." British Standard Institution, UK, 2005.

BS EN 10002-1, "Metallic materials - Tensile testing - Part 1: Method of test at ambient temperature." British Standard Institution, UK, 2001.

ISO, "ISO 834-11:2014(en), Fire resistance tests - Elements of building construction - Part 11: Specific requirements for the assessment of fire protection to structural steel elements," pp. 2016-08-21, 2014.

V. Moliner, A. Espinos, M. L. Romero, A. Hospitaler, and I. C., "Fire behavior of eccentrically loaded slender high strength concrete-filled tubular columns," J. Constr. Steel Res., vol. 83, no. 67, pp. 137-146, 2013.

https://doi.org/10.1016/j.jcsr.2013.01.011

BS EN-1994-1-2, "CEN (European Commitee for Standardization) Eurocode 4 - Design of composite steel and concrete structures - Part 1-2 General rules - Structural fire design," Eurocode 4, vol. 2, no. 2005. 2005.

Published
2021-09-30
How to Cite
Kado, B., Mohammad, S., Lee, Y. H., Shek, P. N., & Ab Kadir, M. A. (2021). EXPERIMENTAL STUDY ON BEHAVIOR OF UNPROTECTED FOAMED CONCRETE FILLED STEEL HOLLOW COLUMN UNDER FIRE. Journal of Civil Engineering, Science and Technology, 12(2), 189-203. https://doi.org/10.33736/jcest.3983.2021